Mitsubishi Electric PWFY error codes
Codes
- 0403Error codeSerial communication error: Serial communication error between the control board and the INV board on the compressor, and between the control board and the Fan board Detail code 01: Between the control board and the INV board Detail code 05: Between the control board and the Fan board
- 1102Error codeAbnormal discharge air temperature: 1) If a discharge temperature of 115 C [239 F] or higher is detected (first detection), units will stop, go into the 3-minute restart delay mode, and automatically restart after three minutes. 2) If a discharge temperature of 115 C [239 F ] or higher is detected again (second detection) within 30 minutes of the first stoppage of the units as described above, units will stop, go into the 3 minute restart delay mode, and automatically restart after three minutes. 3) If a discharge temperature of 1
- 1301Error codeAbnormal low pressure: When starting the compressor from Stop Mode for the first time if low pressure reads 0.098MPa [14psi] immediately before start-up, the operation immediately stops.
- 1302Error codeAbnormal high pressure 1: 1) If a pressure of 3.23MPa [468 psi ] or higher is detected during operation, units will stop, go into the 3 minute restart delay mode, and automatically restart after three minutes. 2) If a pressure of 3.23MPa [468 psi ] or higher is detected again (second detection) within 30 minutes of the first stoppage of the units, units will stop, go into the 3 minute restart delay mode, and automatically restart after three minutes.
- 2000Error codePump interlock error (BU only): Preliminary pump interlock error is detected when the pump interlock circuit becomes open while the units are stopped during Thermo-ON. When a preliminary error is detected, units will go into the Thermo-OFF state and into the restart-prevention mode. When the amount of time listed below has elapsed since the time when a given preliminary error was detected, an error code "2000" will be detected, and the units will come to an abnormal stop. DipSW3-10=OFF 9 seconds *1 DipSW3-10=ON 9 minutes and 5 | Flow switch error (AU only): When the water flow rate of the water supply to the unit is the specified rate or less, the flow switch does not detect, and the unit will be stopped.
- 2134Error codeAbnormal water temperature: In the case of BU and WH, if the value of TH6 becomes equal to or greater than 85°C [185] , units will stop and go into the 3 minute restart delay mode. For a period of thirty minutes after units came to a stop is considered a preliminary error.
- 2135Error codeWater heat exchanger freeze up: Condition 1 1˚C[34] Both TH22 and TH23 of or below have been detected for three minutes in a mode other than Heating Thermo-ON. -15˚C[5] If PWFY is running in Heating Thermo-ON mode TH22 of or below has been detected for 3 continuous when the defrost cycle starts minutes starting from 2 minutes after the start of the defrost cycle. Condition 2 -15˚C[5] If PWFY is running in a mode other than Heating TH22 of or below has been detected for 3 continuous Thermo-ON mode when the defrost cycle starts
- 4102Error codeThe L2 phase current is outside of the specified range. The open phase of the power supply may not always be detected if a power voltage from another circuit is applied.
- 4115Error codePower supply signal sync error: The frequency cannot be determined when the power is switched on.
- 4220Error codeAbnormal bus voltage drop (Detail code 108): If Vdc 200V or less is detected during Inverter operation. (S/W detection) | Bus voltage error (PAM damage) (Detail code 01): PWM circuit error on the INV board is detected. | Abnormal bus voltage rise (Detail code 109): If Vdc 380V is detected during inverter operation. | Converter Fo error (Detail code 121): INV board converter circuit error is detected.
- 4230Error code
- 4250Error codeIPM error (Detail code 101): Overcurrent is detected while power module error detection signal is output. | ACCT overcurrent (H/W detection) (Detail code 102): Overcurrent 34.5Apeak or 16Arm and above is detected
- 5102Error codeTH22 temperature sensor failure (BU, AU): When a short (high temperature intake) or an open (low temperature intake) of the thermistor is detected (the first detection), the outdoor unit stops, turns to anti-restart mode for 3 minutes, and restarts when the detected temperature of the thermistor. When a short or an open is detected again (the second detection) after the first restart of the outdoor unit, the outdoor unit stops, turns to anti-restart mode for 3 minutes, and restarts in 3 minutes when the detected temperature is within th
- 5103Error codeTH13, TH23 temperature sensor failure (BU, AU): When a short (high temperature intake) or an open (low temperature intake) of the thermistor is detected (the first detection), the outdoor unit stops, turns to anti-restart mode for 3 minutes, and restarts when the detected temperature of the thermistor. When a short or an open is detected again (the second detection) after the first restart of the outdoor unit, the outdoor unit stops, turns to anti-restart mode for 3 minutes, and restarts in 3 minutes when the detected temperature is within th
- 5104Error codeTH11 temperature sensor failure (BU): When a short (high temperature intake) or an open (low temperature intake) of the thermistor is detected (the first detection), the outdoor unit stops, turns to anti-restart mode for 3 minutes, and restarts when the detected temperature of the thermistor. When a short or an open is detected again (the second detection) after the first restart of the outdoor unit, the outdoor unit stops, turns to anti-restart mode for 3 minutes, and restarts in 3 minutes when the detected temperature is within th
- 5106Error codeTH6 temperature sensor failure (BU, AU): When a short (high temperature intake) or an open (low temperature intake) of the thermistor is detected (the first detection), the outdoor unit stops, turns to anti-restart mode for 3 minutes, and restarts when the detected temperature of the thermistor. When a short or an open is detected again (the second detection) after the first restart of the outdoor unit, the outdoor unit stops, turns to anti-restart mode for 3 minutes, and restarts in 3 minutes when the detected temperature is within th
- 5108Error codeTH8 temperature sensor failure (BU, AU): When a short (high temperature intake) or an open (low temperature intake) of the thermistor is detected (the first detection), the outdoor unit stops, turns to anti-restart mode for 3 minutes, and restarts when the detected temperature of the thermistor. When a short or an open is detected again (the second detection) after the first restart of the outdoor unit, the outdoor unit stops, turns to anti-restart mode for 3 minutes, and restarts in 3 minutes when the detected temperature is within th
- 5110Error codeHeat sink failure: When a short or an open of THHS is detected just before or during the inverter operation.
- 5201Error codeHigh pressure sensor failure (63HS): If the high pressure sensor detects 0.098MPa [14psi] or less during the operation, the outdoor unit stops once, turns to antirestart mode for 3 minutes, and restarts after 3 minutes when the detected high pressure sensor is 0.098MPa [14psi] or more. If the high pressure sensor detects 0.098MPa [14psi] or less just before the restart, the outdoor unit makes an error stop, and the error code "5201" will appear. During 3-minute antirestart mode, preliminary errors will be displayed on the LED displ
- 5202Error codeLow-pressure sensor fault 2. E rror definition and error detection method
- 5301Error codeACCT sensor short circuit/open circuit: Abnormal value is detected by the ACCT sensor detection circuit immediately before inverter startup. | ACCT sensor fault (Detail code 115): When the formula "output current < 1.5 Arms" remains satisfied for 10 seconds while the inverter is in operation.