Error code
Mitsubishi Electric PWFY code 5108
No approved translation for this record yet; showing the original text.
Meaning
TH8 temperature sensor failure (BU, AU): When a short (high temperature intake) or an open (low temperature intake) of the thermistor is detected (the first detection), the outdoor unit stops, turns to anti-restart mode for 3 minutes, and restarts when the detected temperature of the thermistor. When a short or an open is detected again (the second detection) after the first restart of the outdoor unit, the outdoor unit stops, turns to anti-restart mode for 3 minutes, and restarts in 3 minutes when the detected temperature is within th
Member details
Signed-in members see the LED pattern and how to read the code with the remote control on eligible records.
View details as a memberPossible causes
(4) A pin on the male connector is missing or contact failure (6) Thermistor input circuit failure on the control board
Solution
Solution steps are available to members and are not shown on this page. Answer the questions to open the solution.
Remote technician support
Get help from a technician over a video call.
Address of this page: https://www.remfixit.com/tr/mitsubishi-electric/pwfy/5108