Skip to content
RemFixitSearch fault code

Error code

Mitsubishi Electric PWFY code 5103

No approved translation for this record yet; showing the original text.

Meaning

TH13, TH23 temperature sensor failure (BU, AU): When a short (high temperature intake) or an open (low temperature intake) of the thermistor is detected (the first detection), the outdoor unit stops, turns to anti-restart mode for 3 minutes, and restarts when the detected temperature of the thermistor. When a short or an open is detected again (the second detection) after the first restart of the outdoor unit, the outdoor unit stops, turns to anti-restart mode for 3 minutes, and restarts in 3 minutes when the detected temperature is within th

Member details

Signed-in members see the LED pattern and how to read the code with the remote control on eligible records.

View details as a member

Possible causes

(4) A pin on the male connector is missing or contact failure (6) Thermistor input circuit failure on the control board