Yaskawa CIMR-F7U error codes
Codes
- F1-04Error codeOperation Selection at Deviation PG Deviation Sel
- F1-21Error codeSets the number of pulses for the encoder (pulse generator) for each full rotation of Motor 2
- F7UError codeRated output current (A)
- H1-01Error codeMulti-Function Digital Input Terminal S3 Function Selection Terminal S3 Sel
- H5-01Error codeDrive Node Address Serial Comm Adr
- H5-02Error codeCommunication Speed Selection Serial Baud Rate
- H5-03Error codeCommunication Parity Selection Serial Com Sel
- H5-04Error codeStopping Method After Communication Error Serial Fault Sel
- H5-05Error codeCommunication Fault Detection Selection Serial Flt Dtct
- L1Error code01 Motor Overload Fault Selection ...................5-22
- L1-01Error codeMotor Overload Protection Selection
- L3-01Error codeStall Prevention Selection During Accel StallP Accel Sel
- L3-02Error codeStall Prevention Level During Acceleration StallP Accel Lvl
- L3-03Error codeStall Prevention Limit During Acceleration StallP CHP Lvl
- L3-04Error codeWhen using a braking resistor, use setting “0”. Setting “3” is used in very specific applications. 0: Disabled - The Drive decelerates at the active deceleration rate. If the load is too large or the deceleration time is too short, an OV fault may occur. 1: General Purpose - The Drive decelerates at the active deceleration rate, but if the main circuit DC bus voltage reaches the stall prevention level (380/760 Vdc), deceleration will stop. Deceleration will continue once the DC bus level drops below the stall prevention level. 2: Intelligent - The active deceleration rate is ignored and the Drive decelerates as fast as possible w/o hitting OV fault level. Range: C1-02/10. 3: Stall Prevention w/ Braking Resistor
- L3-05Error codeStall Prevention Selection During Running StallP Run Sel
- L3-06Error codeStall Prevention Level During Running StallP Run Level
- L3-11Error codeOV Suppression Function Selection OV Inhibit Sel
- L3-12Error codeOV Suppression Function Voltage Level OV Inhbt VoltLvl
- L4-03Error codeSpeed Agreement Detection Level (+/-) Spd Agree Lvl +
- L4-05Error codeFrequency Reference Loss Detection Selection Ref Loss Sel
- L4-06Error codeFault Restart
- L5-02Error codeAuto Restart Operation Selec- tion Restart Sel
- n3-01Error codeHigh Slip Braking Deceleration Frequency Width HSB Decel Width
- n3-02Error codeHigh Slip Braking Current Limit HSB Current Ref
- n3-03Error codeHigh Slip Braking Dwell Time at Stop HSB DwelTim@ Stp
- n3-04Error codeHigh Slip Braking Overload Time HSB OL Time
- o1-03Error codeDigital Operator Display Selection Display Scaling
- o2-02Error codeSTOP Key Function Selection Oper STOP Key
- o2-03ParameterUser Parameter Default Value User Defaults
- o2-06Error codeOperation Selection when Digital Operator is Disconnected Oper Detection
- o2-10Error codeCumulative Cooling Fan Operation Time Setting Fan ON Time Set
- o2-12Error codeFault Trace/Fault History Clear Function FLT Trace Init
- o3-01Error codeCopy Function Selection Copy Function Sel
- OH1Error codeHeatsink Overheat The temperature of the Drive’s heatsink exceeded 105 degrees C
- OH2Error codeDrive overheat alarm signal is input from a multi-function digital input terminal S3-S8 (H1-01 to H1-06) that is programmed for B: overheat alarm
- OH3Error codeMotor Overheating 1 Detected when A2 or A3, programmed for motor temperature (H3-09 or H3-05 = E), exceeds 1.17V for time L1-05 and L1-03 = 0 to 2
- OH4Error codeMotor Overheating 2 Detected when A2 or A3, programmed for motor temperature (H3-09 or H3-05 = E), exceeds 2.34V for time L1-05 and L1-03 = 0 to 2
- OL1Error codeMotor Overload Detected when L1-01 = 1 to 3 and the Drive’s output current exceeded the motor overload curve. The overload curve is adjustable using parameter E2-01, L1-01, and L1-02
- OL2Error codeDrive Overload The Drive output current exceeded the Drive’s overload curve
- OL3Error codeOvertorque Detection 1 Drive output current > L6-02 for more than the time set in L6-03 and L6-01 = 3 or 4
- OL4Error codeOvertorque Detection 2 Drive output current > L6-05 for more than the time set in L6-06 and L6-04 = 3 or 4
- OPE01Error codeDrive kVA Setting Error
- OPE03Error codeMulti-function Input Selection Error
- OPE05Error codeRun Command Selection Error The run command selection parameter b1-02 is set to 3 but no option board is installed
- OPE06Error codeControl Method Selection Error
- OPE07Error codeMulti-function Analog Input Error
- OPE08Error codeFunction Selection Error
- OPE09Error codePID Control Setup Error
- OPE10Error codeV/F Parameter Setting Error