Skip to content
RemFixitSearch fault code

Error code

Yaskawa CIMR-F7U code L3-01

No approved translation for this record yet; showing the original text.

Meaning

Stall Prevention Selection During Accel StallP Accel Sel

Member details

Signed-in members see the LED pattern and how to read the code with the remote control on eligible records.

View details as a member

Possible causes

Selects the stall prevention method used to prevent excessive current during acceleration. 0: Disabled - Motor accelerates at active acceleration rate. The motor may stall if load is too heavy or accel time is too short. 1: General Purpose - When output current exceeds L3-02 level, acceleration stops. Acceleration will continue when the output current level falls below the L3-02 level. 2: Intelligent - The active acceleration rate is ignored. Acceleration is completed in the shortest amount of time without exceeding the current value set in L3-02

Solution

Solution steps are available to members and are not shown on this page. Answer the questions to open the solution.

Remote technician support

Get help from a technician over a video call.