Xinje VFD-manual error codes
Codes
- AD-04Error codeAI2 measured voltage 1
- AD-05Error codeAI2 display voltage 1
- AD-06Error codeAI2 measured voltage 2
- AD-07Error codeAI2 display voltage 2
- AD-12Error codeAO1 target voltage 1
- AD-13Error codeAO1 measured voltage 1
- AD-14Error codeAO1 target voltage 2
- AD-15Error codeAO1 measured voltage 2
- AI1Error codeVoltage 0~10V/ Current 0~20mA
- Err01Error code1. There is grounding or short circuit in the output circuit of inverter 2. The control mode is vector control without parameter tuning 3. The acceleration time is too short 4. Improper manual torque lifting or VF curve 5. The voltage is low 6. Start the rotating motor 7. Sudden loading during acceleration 8. The selection of inverter is too small
- Err02Error code1. There is grounding or short circuit in the output circuit of inverter 2. The control mode is vector control without parameter tuning 3. The deceleration time is too short 4. The voltage is low 5. Sudden loading during deceleration 6. There is no additional brake unit and brake resistor
- Err03Error code1. There is grounding or short circuit in the output circuit of inverter 2. The control mode is vector control without parameter tuning 3. The voltage is low 4. Is there sudden load in operation 5. The selection of inverter is too small
- Err04Error code1. High input voltage 2. There is external force to drive the motor during acceleration 3. Acceleration time too short 4. There is no additional brake unit and brake resistor
- Err05Error code1. High input voltage 2. There is external force to drive the motor during deceleration 3. The deceleration time is too short
- Err06Error code1. High input voltage 2. In the process of operation, there is external force to drive the motor
- Err07Error code1. Unstable supply voltage 2. The main control board is abnormal
- Err08Error code1. Instantaneous power failure 2. The input voltage of inverter is not in the range of specification requirements 3. Abnormal bus voltage 4. Abnormal rectifier bridge and buffer resistance 5. Abnormal drive board 6. Abnormal control board
- Err09Error code1. Whether the load is too large or the motor stalls 2. The selection of inverter is too small
- Err10Error code1. Is the setting of motor protection parameters appropriate 2. Whether the load is too large or the motor stalls 3. The selection of inverter is too small
- Err11Error code1. Abnormal three-phase input power supply 2. Abnormal drive board 3. Abnormal lightning protection board 4. The main control board is abnormal
- Err12Error code1. The lead from inverter to motor is abnormal 2. The three-phase output of inverter is unbalanced when the motor is running 3. Abnormal drive board 4. Module is abnormal
- Err13Error code1. The ambient temperature is too high 2. Air duct blocked 3. The fan is damaged 4. Module thermistor damaged 5. Inverter module damaged
- Err14Error code1. Abnormal drive board and power supply 2. The contactor is abnormal
- Err15Error code1. Check the Hall device 2. Abnormal drive board
- Err18Error codeMotor short circuit to ground
- Err19Error codeVFD operation current is lower than P7-61
- Err20Error code1. Whether the load is too large or the motor stalls 2. The selection of inverter is too small
- Err21Error codeThe deviation between the motor parameters and the actual value is too large
- Err43Error code1. Input the signal of external fault through multi-function terminal X 2. Input external fault signal through virtual Y function
- Err44Error code1. The upper computer is not working properly 2. The communication cable is abnormal 3. Incorrect setting of communication parameter group PC
- Err48Error code1. Input user-defined fault 1 signal through multi-function terminal X 2. Input user defined fault 1 signal through virtual IO function
- Err49Error code1. Input user-defined fault 2 signal through multi-function terminal X 2. Input user defined fault 2 signal through virtual IO function
- Err51Error codeIn the process of inverter operation, change the current motor selection through the terminal
- Err52Parameter1. Encoder parameter setting incorrect 2. Motor blocked
- Err53Error code1. Incorrect setting of encoding parameters 2. The motor is not tuned 3. Unreasonable setting of motor over speed detection parameters P7-63 and P7-64
- Err54Error code1. Loose wiring of temperature sensor 2. Motor temperature too high
- is3Error codeDuring rapid acceleration, there is a high possibility of motor stall. This can be achieved by adjusting the P5-22 overcurrent stall action current compensation coefficient to a set value of 100%
- P0-01Error codeFirst motor control mode selection
- P0-02Error codeOperation command channel selection
- P0-03Error codeMain frequency source A channel selection
- P0-04Error codeAuxiliary frequency source B channel selection
- P0-14Error codeUpper limit frequency source
- P0-25Error codeMotor parameter group selection
- P1-00Error codeMotor type selection
- P1-01Error codeMotor rated power / voltage / current / frequency / speed
- P1-02Error codeMotor rated voltage
- P1-03Error codeMotor rated current
- P1-04Error codeMotor rated frequency
- P1-05Error codeMotor rated speed
- P1-06Error codeEquivalent stator resistance, inductance and rotor inductance of the motor