Yaskawa All models error codes
Codes
- oPE03Error codeÇok fonksiyonlu kontak giriúleri H1-01'den H1-08'e kadar ters bir ayar atandı. • Aynı fonksiyon iki giriúe atandı. ("Harici hata" ve "Kullanılmaz" hariçtir) • Baúka giriú fonksiyonlarının ayarını gerektiren giriú fonksiyonları tek olarak ayarlandı. • Eúzamanlı kullanılmasına izin verilmeyen giriú fonksiyonları ayarlandı
- oPE05Error code• Çalıúma komutu kayna÷ı (b1-02) veya frekans referansı kayna÷ı (b1-01) 3'e ayarlanmıú, fakat herhangi opsiyon kartı monte edilmemiú. • Frekans referans kayna÷ı, darbe giriúine ayarlanmıú, fakat H6-01 "0" de÷ildir
- oPE07Error codeMulti-Function Analog Input Selection Error
- oPE08Error codeError Name
- oPE09Error codePID Control Selection Error
- oPE10Error codeV/f Data Setting Error
- oPE11Error codeCarrier Frequency Setting Error
- oPE13Error codePulse Train Monitor Selection Error
- oPE16Error codeEnergy Saving Constants Error
- oPE18Error codeOnline Tuning, OLV (A1-02 = 2)'de etkin iken aúa÷ıdaki ayar hatalarından biri oluútu. • E2-02, orijinal fabrika ayar de÷erinin %30'unun altına ayarlandı • E2-06, orijinal fabrika ayar de÷erinin %50'sinin altına ayarlandı • E2-03 = 0
- oPE27Error codeBP Program Error
- oPE28Error codeSequence Timer Error
- oPE29Error codeBaud Rate Setting Error
- ovError codeAşırı Voltaj ( devamı >> )
- OV1Error codeOvervoltage during accel
- ov2Error codeBus voltage is boosted because the motor cable is too long
- PE01Error codeSürücü Birimi Ayar Hatası
- PFError codePower supply fault
- Pn520Error codeCheck the alarm level (Pn520) to see if it is set to an appropriate value
- S1Error codeS7 terminal giriş sinyali arızası
- S2Error codeDigital Operator
- S3Error codeFactory setting is " Fault Reset " (1)
- S3-02Error codeSets the voltage level that triggers drive built-in the braking transistor
- S4Error codedrive, and reset the fault Resetting via Fault Reset Digital Input S4
- S4-04Error codeSets the level of voltage fluctuation in the DC bus that triggers KEB
- S4-05Error codeSets the time required for the voltage fluctuation level defined in S4-04 to trigger KEB
- S4-07Error codeSets the time for that the DC bus voltage must exceed the level set in S4-06 in order to end the KEB function and reaccelerate to the set frequency reference
- S4-08Error codeDefines the DC bus voltage ripple that indicates a one phase loss, thus triggering the KEB function
- S4-10Error codeSets the time that the ripple in the DC bus voltage must exceed the level set in S4-08 to trigger one phase loss detection
- S4-11Error codeWhen KEB 1 or KEB 3 is selected, the drive attempts to keep the DC bus voltage at the traget voltage defined in S4-11 multiplied by E1-01
- S4-14Error codeSets the frequency level to prohibit re-acceleration after the power returned. If the drive output frequency fell below S4-14 during KEB operation the drive will decelerate the motor to stop, even if the power returns
- S6-02Error codeThe time required for the motor to accelerate from zero up to the maximum frequency at the rated torque. If E2- 11 is changed by the user or by performing Auto- Tuning, then S6-02 will automatically be set to the value of a Yaskawa 4-pole motor
- S6-04Error codeSets the gain to keep the voltage in the DC bus at the target level. If overvoltage or undervoltage is a problem at the start of Power KEB, gradually increasing S6-04 in increments of 0.1 may help
- S7Error codeLED Operator Display
- SCError codeShort circuit
- T1Error codeDrive output
- T1-03ParameterThe torque reference exceeded 20% during Auto-Tuning. The results from Auto-Tuning the no-load current exceeded 80%. LED Operator Display Cause Motor data entered during Auto-Tuning was incorrect. Auto-Tuning calculated values outside the parameter setting range, assigning the iron-core saturation c
- T1-06Error codeSets the number of motor poles
- T1-11Error codeProvides the iron loss for determining the Energy Saving coefficient. The value set to E2-10 (motor iron loss) when the power is cycled. If T1-02 is changed, an initial value valid for the selected capacity will be shown
- T2Error code• Check the motor wiring for a short between motor lines. • If a magnetic contactor is used between motors, ensure it is on. • Replace the drive
- to40Error code7 (Swing PWM 1)
- to67HError codeDrive output current (or torque in OLV) less than L6-02 for longer than L6-03 time
- U-05Error codeMain circuit DC voltage can be monitored
- U-09Error codeLast four fault history is displayed. (see paragraph 4.4)
- U1-03Error codeDisplays the output current
- U1-05Error codeDisplays the motor speed feedback. Display units are determined by o1-03
- U1-06Error codeDisplays the output voltage
- U1-07Error codeDisplays the DC bus voltage
- U1-08Error codeDisplays the output voltage (this value is determined internally)
- U1-11Error codeDisplays the output terminal status. Multi-Function Digital Output (fault) (terminal MA/MB-MC) Multi-Function Digital Output 1 (terminal P1) enabled Multi-Function Digital Output 2 (terminal P2) enabled