Value flanş açma takımı All models error codes
Codes
- F6Error code• If 21 has 24vdc and 22 has no voltage. Detach and reseat the aux contact. • If the input does change state. Verify that the there is an x in the brackets when the input is high and no x when the input is low. • If the X does not appear when the input is high move the input to an unused input
- F11Error codeThe contactor is closed or pulled in. o Is the pick relay picked? If it is trouble shoot your pick relay. o If it is not measure voltage at A1 to N. If there is voltage at A1 (around 120vac) there is a wiring mistake to the coil of the contactor. o If there is no voltage, the contactor it is stuck or welded closed.
- F49Error codeF49: Drive Fault
- F53Error codeF53: Fault Log Cleared
- F91Error codeF91: Learn Error
- F122Error codeF122: Low Pressure
- F128Error codeF128: Overloaded
- F200Error codeF200: Software Error
- F219Error codeF219: Flood Sensor
- L1000Error codeLocated on the top right corner of the smart rise SRU. o Verify the correct wiring to the drive. It is on page 4 of your prints. Spd Command Src, Run Command Src, Fault o Reset Src, Brake Pick Src, and Brake Hold Src are all set to SERIAL. o Go to the C1 menu on the Magnetek drive and verify that serial mode is set to MODE1 o Replace Cat 5 cable going from the MR board to the drive. o Re-program the CT/COP board as the MR and vice versa. o If the fault continues there is a problem with the drives communication board.