Trox VAV kutusu All models error codes
Codes
- ast10Error codeEspecially for VAV terminal units for room pressure control Is the cross-section of the pressure measurement line sufficient? (Especially with ring lines for recording the reference pressure) Are pressure-controlled rooms sufficiently leakproof? Do pressure-controlled rooms have sufficient air transfer (at least 10% of the total extract air)? Were all doors and seals installed for adjustment? Holes and walls are sealed? Does the pressure reference measurement take place in a pressure-stable range?
- D3AError codeSupply voltage
- DD15Error codeSupply voltage
- V2Error code Characteristic curve of the setpoint value control matching the control com- ponent or its set characteristic curve parameterisation? Example: Operating mode V2 = characteristic 2-10 V DC; also see silver adjustment sticker and product data sheets of the control components Zero point correction performed on control components with static trans- ducer? Only required for control components TUN, TUNF, TUS, TUSD, ELAB. If necessary, adapt the actuators again (only required for certain control components)