Trox VAV kutusu All models code ast10

No approved translation for this record yet; showing the original text.

Meaning

Especially for VAV terminal units for room pressure control  Is the cross-section of the pressure measurement line sufficient? (Especially with ring lines for recording the reference pressure)  Are pressure-controlled rooms sufficiently leakproof?  Do pressure-controlled rooms have sufficient air transfer (at least 10% of the total extract air)?  Were all doors and seals installed for adjustment? Holes and walls are sealed?  Does the pressure reference measurement take place in a pressure-stable range?