- U1Arıza kodu
- U2Arıza kodu
- U3Arıza kodu
- U4Arıza kodu
- U6Arıza koduCompressor over current (overload) breaking Abnormal if current value exceeds overload set value during compressor operation. P71V• 23.5A P71Y• 7.8A • • • • P100V• 28.5A P100Y• 9.4A • • • • P125Y• 12.6A P140Y• 15.6A • • • •
- UAArıza koduThermal relay (51C) worked Abnormal if 51C is open.
- UDArıza koduOver heat protection (over-load operation protection/abnormal fan) Abnormal if pipe thermistor detects the value that exceeds set value during compressor operation. P71-P140• 70: • •
- UEArıza kodu
- UFArıza koduCompressor over current (start-up locked) breaking Abnormal if compressor current exceeds 1.2 times of overload set value.
- UHArıza kodu