Phoenix Contact ev şarj istasyonu All models error codes
Codes
- D2Error code≤ 20 A or ≤ 13 A current carrying capacity selection (only when DIP 1 is set to ON)
- D3Error code≤ 13 A current carrying capacity selection (only when DIP 1 is set to ON)
- I1Error codeCurrent of the three phases in A
- I3Error codeMonitoring of charging currents - “enabled”: the charging controller compares the measured charging currents with the maximum permissible charging currents specified by the PWM signal on the Control Pilot. In the event of an overcurrent of 10% ... 20%, the charging process is aborted after 100 s. In the event of an overcurrent > 20%, it is switched off after 10 s. The charging con- troller enters an error state, the reset condition is status A. - “disabled”: no monitoring of charging currents
- or20Error codeDevice rejects EV charging because current carrying capacity of charging cable is too low
- S1Error codeStatus B
- S2Error codeStatus C
- S3Error codeStatus B
- S4Error codeStatus A
- S5Error codeThe charging cable is connected to the device. The resistance value of 680 ohms is detected at the Proximity Plug. This value indicates to the device that the cable or plug has a current carrying capacity of 20 A
- S6Error codeStatus D
- S7Error codeStatus C
- S8Error codeStatus B
- S9Error codeStatus A
- S10Error codeStatus B
- S11Error codeStatus A
- S12Error codeStatus B
- S13Error codeStatus A
- V1Error codeVoltage at the three phases in volts, either as outer conductor voltage or voltage to neutral conductor, depends on the configuration and the data provided by the meter
- V1VError codeDevice switches the “ventilator” relay ON