Yaskawa All models error codes
Codes
- F6-03Error code• Remove the cause of the external fault. • Remove the external fault input from the PLC
- F6-04Error codeSet the delay time for error detection if a bus error occurs
- F6-11Error codeCommunication Speed
- F6-14Error codeSelects if a BUS fault can be automatically reset. 0: Disabled 1: Enabled
- F6-25Error codeDetermines how the drive should stop if a MECHATROLINK-II watchdog timer error occurs (E5). 0: Ramp to stop (uses the deceleration time in C1-02) 1: Coast to stop 2: Fast Stop (uses the deceleration time in C1-09) 3: Continue operation (alarm only)
- F6-26Error codeSets the number of times allowed for a MECHATROLINK- II bUS error to be detected
- F6-36Error codeCommunication Speed
- F6-41Error codeCommunication Speed
- F6-51Error codeCommunication Speed
- F6-54Error codeSelects if a EF0 fault is detected when no data are received from the master. 0: Disabled 1: Enabled
- F6-55Error codeCommunication Speed
- F6-62Error codeSets the heartbeat interval for DeviceNet communications
- F7Error codeNetwork Communications
- F7-16Error codeSets the timeout value for communication loss detection
- Fn1Error codeExternal Fan Fault
- GA700Error codeControl power fault
- GFError codeToprak Hatası ( devamı >> )
- H1Error codeEF
- H1-03Error code24: External Fault
- H1-04Error code14: Fault Reset
- H3-01Error codeThe drive has been set to accept the frequency reference from the incorrect source. The terminal set to accept the main speed reference is set to the incorrect voltage and/or current. Selection for the sink/source mode is incorrect. Frequency reference is too low. Multi-function analog input is set
- H3-02Error codeMulti-function analog input is set up to accept gain for the frequency reference, but no voltage (current) has been provided. The STOP button was pressed when the drive was started from a REMOTE source. Motor is not producing enough torque in the V/f motor control method. Motor is not producing enou
- H3-03Error codeThe analog input gain and bias for the frequency reference input are set to incorrect values. A frequency bias signal is being entered via analog input terminals A1 to A2. PI control is enabled, and the drive is consequently adjusting the output frequency to match the PI setpoint. The drive will onl
- H3-09Parameter
- H3-10Error codeError Name
- H3-13Error codeNo PID feedback input. The level of detection and the target value do not correspond with each other. Reverse drive output frequency and speed detection. When output frequency rises, the sensor detects a speed decrease.
- H4-01Error code00408 (heatsink plate temperature)
- H4-02Error codeSets terminal AM output gain. Maximum output voltage is 10 V
- H5Error codeMEMOBUS/Modbus Serial Communication ........................................................................185
- H5-02Error codeCommunication Speed
- H5-04Error codeSelects the stopping method when a communication time- out fault (CE) is detected. 0: Ramp to stop 1: Coast to stop 2: Fast-stop 3: Alarm only
- H5-05Error codeEnables or disables the communications time-out fault (CE) detection. 0: Disabled 1: Enabled - If communication is lost for more than two seconds, a CE fault will occur
- H5-09Error codeSets the time required to detect a communications error. Adjustment may be need when networking several drives
- H5-11Error codeCommunications ENTER Function Selection
- H6-01Error codeoPE07
- han10Error codeThe drive is operating at less than 10% of the speed reference
- Hxx130Error code(Connection device name): Error response received on a read out request (General status: [Hex] Extended status [Hex]
- Hxx131Error code(Connection device name): Error response received on a write request (General status: [(Hex)] Extended status [(Hex)])
- ing122Error codeFault Display
- is7Error code• Cycle power to the drive. Check if the fault reoccurs. • Replace the drive if the fault continues to occur
- L1Error codeMotor Protection Functions ..................................................................................................188
- L1-01Error codeMotor Protection Function Selection
- L1-02Error codeSets the motor thermal overload protection (oL1) time. A larger L1-02 time will increase the time for an oL1 fault to occur. This parameter does not typically require adjustment. Should be set in accordance with the overload tolerance of the motor
- L1-03Error codeSets operation when the motor temperature analog input (H3-02/10 = E) exceeds the oH3 alarm level. 0: Ramp to Stop 1: Coast to Stop 2: Fast-stop using C1-09 3: Alarm Only (“oH3” will flash)
- L1-04Error codeSets stopping method when the motor temperature analog input (H3-02/10 = E) exceeds the oH4 fault level. 0: Ramp to Stop 1: Coast to Stop 2: Fast-stop
- L2-01Error codeEnables and disables the momentary power loss function. 0: Disabled - Drive trips on (Uv1) fault when power is lost. 1: Power Loss Ride-Thru Time - Drive will restart if power returns within the time set in L2-02. 2: CPU Power Active - Drive will restart if power returns as long as the CPU is working
- L2-02Error code
- L2-03Error codeSets the minimum wait time for residual motor voltage decay before the drive output reenergizes after power loss Ride- Thru. If L2-03 is greater than L2-02, operation resumes after the time set in L2-03
- L2-04Error codeSets the time for the output voltage to return to the preset V/ f pattern during Speed Search
- L2-05Error codeUv detection voltage