Xinje VFD-manual All models error codes
Codes
- A9-17Error codeİletişim adresi haritalama görüntüsü 3
- A9-18Error codeİletişim adresi haritalama görüntüsü 4
- A9-19Error codeİletişim adresi haritalama görüntüsü 5
- A9-20Error codeİletişim adresi haritalama görüntüsü 6
- A9-21Error codeİletişim adresi haritalama görüntüsü 7
- A9-22Error codeİletişim adresi haritalama görüntüsü 8
- A9-23Error codeİletişim adresi haritalama görüntüsü 9
- A9-24Error codeİletişim adresi haritalama görüntüsü 10
- A9-25Error codeİletişim adresi haritalama görüntüsü 11
- A9-26Error codeİletişim adresi haritalama görüntüsü 12
- A9-27Error codeİletişim adresi haritalama görüntüsü 13
- A9-28Error codeİletişim adresi haritalama görüntüsü 14
- AD-00Error codeAI1 measured voltage 1
- AD-01Error codeAI1 display voltage 1
- AD-02Error codeAI1 measured voltage 2
- AD-03Error codeAI1 display voltage 2
- AD-04Error codeAI2 measured voltage 1
- AD-05Error codeAI2 display voltage 1
- AD-06Error codeAI2 measured voltage 2
- AD-07Error codeAI2 display voltage 2
- AD-08Error codeAI3 measured voltage 1
- AD-09Error codeAI3 display voltage 1
- AD-10Error codeAI3 measured voltage 2
- AD-11Error codeAI3 display voltage 2
- AD-12Error codeAO1 target voltage 1
- AD-13Error codeAO1 measured voltage 1
- AD-14Error codeAO1 target voltage 2
- AD-15Error codeAO1 measured voltage 2
- AD-16Error codeAO2 target voltage 1
- AD-17Error codeAO2 measured voltage 1
- AD-18Error codeAO2 target voltage 2
- AD-19Error codeAO2 measured voltage 2
- AI1Error codeVoltage 0~10V Current 0~20mA
- AI2Error codeVoltage 0~10V Current 0~20mA
- AO1Error codeVoltage 0~10V Current 0~20mA
- Err01Error code1. There is grounding or short circuit in the output circuit of frequency converter 2. The control mode is vector control without parameter tuning 3. The acceleration time is too short 4. Improper manual torque lifting or VF curve 5. The voltage is low 6. Start the rotating motor 7. Sudden loading during acceleration 8. The selection of frequency converter is too small
- Err02Error code1. There is grounding or short circuit in the output circuit of frequency converter 2. The control mode is vector control without parameter tuning 3. The deceleration time is too short 4. The voltage is low 5. Sudden loading during deceleration 6. There is no additional brake unit and brake resistor
- Err03Error code1. There is grounding or short circuit in the output circuit of frequency converter 2. The control mode is vector control without parameter tuning 3. The voltage is low 4. Is there sudden load in operation 5. The selection of frequency converter is too small
- Err04Error code1. High input voltage 2. There is external force to drive the motor during acceleration 3. Acceleration time too short 4. There is no additional brake unit and brake resistor
- Err05Error code1. High input voltage 2. There is external force to drive the motor
- Err06Error code1. High input voltage 2. In the process of operation, there is external force to drive the motor
- Err07Error code1. Unstable supply voltage 2. The main control board is abnormal
- Err08Error code1. Instantaneous power failure 2. The input voltage of frequency converter is not in the range of specification requirements 3. Abnormal bus voltage 4. Abnormal rectifier bridge and buffer resistance 5. Abnormal drive board 6. Abnormal control board
- Err09Error code1. Whether the load is too large or the motor stalls 2. The selection of frequency converter is too small
- Err10Error code1. Is the setting of motor protection parameters appropriate 2. Whether the load is too large or the motor stalls 3. The selection of frequency converter is too small
- Err11Error code1. Abnormal three-phase input power supply 2. Abnormal drive board 3. Abnormal lightning protection board 4. The main control board is abnormal
- Err12Error code1. The lead from inverter to motor is abnormal 2. The three-phase output of inverter is unbalanced when the motor is running 3. Abnormal drive board 4. Module is abnormal
- Err13Error code1. The ambient temperature is too high 2. Air duct blocked 3. The fan is damaged 4. Module thermistor damaged 5. Inverter module damaged
- Err14Error code1. Abnormal drive board and power supply 2. The contactor is abnormal
- Err15Error code1. Check the Hall device 2. Abnormal drive board