- C074Error codeCommunication parity selection
- C075Error codeCommunication stop bit selection
- C076Error codeSelects inverter response to communications error. Five options: 00... Trip (error code E60) 01... Decelerate to a stop and trip (error code E60) 02... Disable 03... Free run stop (coasting) 04... Decelerate to a stop
- C077Error codeSets the communications watchdog timer period. Range is 0.00 to 99.99 sec
- C078Error codeCommunication wait time
- C081Error codeScale factor between the external frequency command on terminals L - O (voltage input) and the frequency output, range is 0.0 to 200.0%
- C082Error codeScale factor between the external frequency command on terminals L - OI (current input) and the frequency output, range is 0.0 to 200.0%
- C241Error codeOverload level setting, 2nd motor
- D001Error codeReal-time display of output frequency to motor, from 0.0 to 400.0 Hz
- D002Error codeFiltered display of output current to motor (100 ms internal filter time constant), range is 0 to 200% of inverter rated current
- D013Error codeVoltage of output to motor, range is 0.0 to 600.0V
- D081Error codeDisplays trip event informa- tion: • Error code • Output freq. at trip point • Motor current at trip point • DC bus voltage at trip point • Cumulative inverter opera- tion time at trip point • Cumulative power-ON time at trip point
- E1Error codeA malfunction in the built-in CPU has occurred, so the inverter trips and turns OFF its output to the motor
- E02Error codeOver-current event during deceleration
- E2Error codeWhen the inverter internal temperature is above the threshold, the thermal sensor in the inverter module detects the excessive temperature of the power devices and trips, turning the inverter output OFF
- E03Error codeOver-current event during acceleration
- E3Error codeAn internal inverter error has occurred at the safety protection circuit between the CPU and main driver unit. Excessive electrical noise may be the cause. The inverter has turned OFF the IGBT module output
- E04Error codeOver-current event during other conditions
- F001Error codeStandard default target frequency that determines constant motor speed, range is 0.0 / start frequency to 400 Hz
- F202Error codeStandard default acceleration, 2nd motor, range is 0.01 to 3000 sec
- F203Error codeStandard default deceleration, 2nd motor, range is 0.01 to 3000 sec
- H006Error codeMotor constant (factory set), range is 0 to 255
- H203Error codeMotor capacity, 2nd setting
- H204Error codeMotor poles setting, 2nd motor
- H206Error codeMotor constant (factory set), range is 0 to 255
- P045Error codeFive options: 00... Trip (Error Code E70) 01... Decelerate to stop and trip (Error Code E70) 02... Hold last speed 03... Free run stop 04... Decelerate and stop
- P048Error codeFive options: 00... Trip (Error Code E70) 01... Decelerate to stop and trip (Error Code E70) 02... Hold last speed 03... Free run stop 04... Decelerate and stop