Codes
- L1Error codeGenerator L1, L2 or L3 voltage was under the Gen <V BOC limit for Gen V del time. Undervoltage protections are based on Gener protect: Gen <V BOC and Gen V del Setpoints. This alarm is issued if voltage protections are based on phase to neutral voltages. It means that Basic settings: FixVoltProtSel is set to PHASE-NEUTRAL.19)
- L12Error codeGenerator L12, L23 or L31 voltage was under the Gen <V BOC limit for Gen V del time.. Undervoltage protections are based on Gener protect:Gen <V BOC and Gen V delSetpoints. This alarm is issued if voltage protections are based on phase to phase voltages. It means that Basic settings:FixVoltProtSel is set to PHASE-PHASE.19)
- L23Error codeIf the value of 10 min. average mains voltage of any phase (Mains Avg V1, Mains Avg V2, Mains Avg V3) exceed value given by Setpoint Mains Avg >V MP (Mains protect group) the MCB is opened and message Mains Avg x >V appears in alarm list and history record. BO Common MP is activated (x indicates number of phase)