Yaskawa inverter CIMR-VC All models code L8-03
No approved translation for this record yet; showing the original text.
Meaning
Sets the drive operation when an overheat alarm oH is detected. 0: Ramp to Stop using the active decel time. 1: Coast to Stop. 2: Fast-stop using the time set in C1-09. 3: Alarm Only. Drive continues running, but displays an alarm. 4: Reduced Speed Operation. Drive continues to run with reduced frequency reference as specified in L8-19. Settings 0 through 2 trigger a fault relay if the heatsink becomes too hot
Member details
Signed-in members see the LED pattern and how to read the code with the remote control on eligible records.
View details as a memberSolution
Solution steps are available to members and are not shown on this page. Answer the questions to open the solution.