Sodeca çatı fanı All models code P-16

No approved translation for this record yet; showing the original text.

Meaning

  = Uni-polar 0 to 10 Volt Signal. The drive will remain at minimum speed (P-02) if the analog reference after scaling and offset are applied is =<0.0%. 100% signal means the output frequency / speed will be the value set in P-01.   = Uni-polar 0 to 10 Volt Signal, bi-directional operation. The drive will operate the motor in the reverse direction of rotation if the analog reference after scaling and offset are applied is <0.0%. e.g. for bidirectional control from a 0 - 10 volt signal, set P-35 = 200.0%, P-39 = 50.0%.   = 0 to 20mA Signal.   = 4 to 20mA Signal, the VSD will trip and show the fault code  500ms after the signal level falls below 3mA.   = 4 to 20mA Signal, the VSD will run at Preset Speed 1 (P-20 if the signal level falls below 3mA.   = 20 to 4mA Signal, the VSD will trip and show the fault code  500ms after the signal level falls below 3mA.   = 20 to 4mA Signal, the VSD will run at Preset Speed 1 (P-20 if the signal level falls below 3mA.   = 10 to 0 Volt Signal (Uni-polar). The drive will operate at Maximum Frequency / Speed if the analog reference after scaling and offset are applied is =<0.0%