Error code

Mitsubishi Electric SLZ code PL

No approved translation for this record yet; showing the original text.

Meaning

Abnormal refrigerant circuit During Cooling, Drying, or Auto Cooling operation, the following conditions are regarded as failures when detected for 1 second. a) The compressor continues to run for 30 or more seconds. b) The liquid pipe temperature (TH2) or the condenser/evaporator temperature (TH5) is 167°F [75°C] or more. These detected errors will not be cancelled until the power source is reset.

Member details

Signed-in members see the LED pattern and how to read the code with the remote control on eligible records.

View details as a member

Possible causes

(1) Abnormal operation of 4-way valve (2) Disconnection of or leakage in refrigerant pipes Air into refrigerant piping Abnormal operation (no rotation) of indoor fan · Defective fan motor · Defective indoor control board Defective refrigerant circuit (restriction)

Solution

Solution steps are not shared for faults that may be dangerous.

No do-it-yourself solution is given for this fault. For your safety, call an authorised service.