Error code
Mitsubishi Electric SLZ code P6
For your safety
This fault is rated high and involves an area that affects personal safety. No remote repair or do-it-yourself instructions are given; do not use the appliance or try to open or repair it.
Hazard area: mains voltage and refrigerant gas circuit
Do not use the appliance and call an authorised service. If there is a risk to life, move to a safe place and see the emergency numbers.
The emergency numbers here are for Turkey. If you are outside Turkey, call your local emergency number.
No approved translation for this record yet; showing the original text.
Meaning
Freezing/overheating protection is operating Freezing protection (Cooling mode) 1 The unit is in 6-minute resume prevention mode if pipe <liquid or condenser/evaporator> temperature stays under -15°C for 3 minutes after the compressor started. Abnormal if it stays under 15°C for 3 minutes again within 16 minutes after 6-minute resume prevention mode. 2 Overheating protection (Heating mode) The units is in 6-minute resume prevention mode if pipe <condenser / evaporator> temperature is detected as
Member details
Signed-in members see the LED pattern and how to read the code with the remote control on eligible records.
View details as a memberPossible causes
(Cooling or drying mode) (1) Clogged filter (reduced airflow) (2) Short cycle of air path (3) Low-load (low temperature) operation out of the tolerance range (4) Defective indoor fan motor • Fan motor is defective. • Indoor controller board is defective. (5) Defective outdoor fan control (6) Overcharge of refrigerant (7) Defective refrigerant circuit (clogging) (Heating mode) (3) Overload (high temperature) operation out of the tolerance range (8) Bypass circuit of outdoor unit is defective.
Solution
Solution steps are not shared for faults that may be dangerous.
No do-it-yourself solution is given for this fault. For your safety, call an authorised service.