Mitsubishi Electric PUZ code U2

No approved translation for this record yet; showing the original text.

Meaning

(TH4: 1102) (TH33: 1132): High discharge temperature High comp. surface temperature (1) Abnormal if discharge temperature thermistor (TH4) exceeds 248˚F [120:] or 230˚F [110:] continuously for 5 minutes. Abnormal if condenser/evaporator temperature thermistor (TH5) exceeds 104˚F [40:] during defrosting and discharge temperature thermistor (TH4) exceeds 230˚F [110:]. (2) Abnormal if discharge superheat (Cooling: TH4−TH5 Heating: TH4−TH6) increases. All the conditions in A or B are detected simultaneously for 10 minutes co

Member details

Signed-in members see the LED pattern and how to read the code with the remote control on eligible records.

View details as a member

Possible causes

controller board (5) Disconnection or contact failure of 63H connection (6) Defective outdoor controller board (7) Defective action of linear expansion valve (8) Malfunction of fan driving circuit (1) Overheated compressor operation caused by shortage of refrigerant (2) Defective operation of stop valve (3) Defective thermistor (4) Defective outdoor controller board (5) Defective action of linear expansion valve

Solution

Solution steps are not shared for faults that may be dangerous.

No do-it-yourself solution is given for this fault. For your safety, call an authorised service.