Error code
Mitsubishi Electric PUY code 1500
No approved translation for this record yet; showing the original text.
Meaning
Overcharged refrigerant abnormality: 1. If the discharge SH 10K is detected during operation (at first detection), the outdoor unit stops at once. The 3 minutes restart prevention mode is entered. After three minutes, the outdoor unit starts up again. 2. If the discharge SH 10K is detected again within 30 minutes after the outdoor unit stops (second detection), an abnormal stop is applied, and “1500” is displayed. 3. If discharge SH 10K is detected more than 30 minutes after the outdoor unit stops, the state is the same as the firs
Member details
Signed-in members see the LED pattern and how to read the code with the remote control on eligible records.
View details as a memberPossible causes
(1) Excessive refrigerant charge. (2) Main circuit board thermistor input circuit trouble. (3) Thermistor mounting trouble (TH11, TH12).
Solution
Solution steps are not shared for faults that may be dangerous.
No do-it-yourself solution is given for this fault. For your safety, call an authorised service.
Remote technician support
Get help from a technician over a video call.
Address of this page: https://www.remfixit.com/tr/mitsubishi-electric/puy/1500