Skip to content
RemFixitSearch fault code

Error code

Mitsubishi Electric PURY code 5115

No approved translation for this record yet; showing the original text.

Meaning

Compressor shell bottom temperature sensor (TH15) fault (Outdoor unit): When a short (high temperature intake) or an open (low temperature intake) of the thermistor is detected (the first detection), the outdoor unit stops, turns to anti-restart mode for 3 minutes, and restarts when the detected temperature of the thermistor. The unit will continue its operation by using other sensors as a backup. Detection of a shortor open-circuit as described above is suspended during the defrost cycle and for 3 minutes after the operation mode is changed.

Member details

Signed-in members see the LED pattern and how to read the code with the remote control on eligible records.

View details as a member

Possible causes

(2) Pinched lead wire (3) Torn wire coating Troubleshooting (4) A pin on the male connector is missing or contact failure (5) Disconnected wire (6) Thermistor input circuit failure on the control board (1) Thermistor failure (3) Torn wire coating (4) A pin on the male connector is contact failure (6) Thermistor input circuit failure Codes board

Solution

Solution steps are not shared for faults that may be dangerous.

No do-it-yourself solution is given for this fault. For your safety, call an authorised service.

Remote technician support

Get help from a technician over a video call.