Meaning
LEV4 outlet temperature sensor (TH14) fault (BC controller): If a shorted (high temperature intake) or open (low temperature intake) thermistor (TH11, TH12, TH14, TH15, or TH16) is detected during operation, and an error code "5111," "5112," "5114," "5115," or "5116" will appear. The unit will continue its operation by using other sensors as a backup. Detection of a shortor open-circuit as described above is suspended during the defrost cycle and for 3 minutes after the operation mode is changed.
Member details
Signed-in members see the LED pattern and how to read the code with the remote control on eligible records.
View details as a memberPossible causes
(1) Thermistor failure (2) Pinched lead wire (3) Torn wire coating (4) A pin on the male connector is contact failure (5) Disconnected wire (6) Thermistor input circuit failure Codes board
Solution
Solution steps are available to members and are not shown on this page. Answer the questions to open the solution.