Mitsubishi Electric PURY code 5110

No approved translation for this record yet; showing the original text.

Meaning

Heatsink temperature sensor (THHS) fault (Detail code 01): When a short or an open of THHS is detected just before or during the inverter operation.

Member details

Signed-in members see the LED pattern and how to read the code with the remote control on eligible records.

View details as a member

Possible causes

(1) INV board failure (1) THHS sensor failure (2) Contact failure (1) INV board failure If the problem (1) Thermistor failure (2) Pinched lead wire (3) Torn wire coating (4) A pin on the male connector is missing or contact failure (5) Disconnected wire (6) Thermistor input circuit failure on the control board

Solution

Solution steps are available to members and are not shown on this page. Answer the questions to open the solution.