Mitsubishi Electric PURY code 5108

No approved translation for this record yet; showing the original text.

Meaning

SC coil bypass outlet (TH8): 2.When a short or an open is detected again (the second detection) after the first restart of the outdoor unit, the outdoor unit stops, turns to anti-restart mode for 3 minutes, and restarts in 3 minutes when the detected temperature is within the normal range. 3.When a short or an open is detected again (the third detection) after the previous restart of the outdoor unit, the outdoor unit makes an error stop. 4.When a short or an open of the thermistor is detected just before the restart of the

Member details

Signed-in members see the LED pattern and how to read the code with the remote control on eligible records.

View details as a member

Possible causes

(5) Disconnected wire (6) Thermistor input circuit failure on the main board Short detection TH1 240 C [464 F ] and above TH5 110 C [230 F ] and above TH6 110 C [230 F ] and above TH7 70 C [158 F ] and above TH8 70 C [158 F ] and above