Error code
Mitsubishi Electric PURY code 4250
For your safety
This fault is rated high and involves an area that affects personal safety. No remote repair or do-it-yourself instructions are given; do not use the appliance or try to open or repair it.
Hazard area: mains voltage and refrigerant gas circuit
Do not use the appliance and call an authorised service. If there is a risk to life, move to a safe place and see the emergency numbers.
The emergency numbers here are for Turkey. If you are outside Turkey, call your local emergency number.
No approved translation for this record yet; showing the original text.
Meaning
DCCT overcurrent (H/W detection) (Detail code 103) Instantaneous overcurrent (Detail code 106) Overcurrent (effective value) (Detail code 107): Overcurrent 106 Apeak or 64 Arms and above is detected by the current sensor. | Instantaneous overcurrent (Detail code 106) Overcurrent (effective value) (Detail code 107): Overcurrent 56 Apeak or 33 Arms and above is detected by the current sensor.
Member details
Signed-in members see the LED pattern and how to read the code with the remote control on eligible records.
View details as a memberPossible causes
(1) Inverter output related (1) Grounding fault compressor (2) Inverter output related (1) Grounding fault of fan motor (2) Fan board failure (1) Short - circuited compressor (2) Output wiring (1) Short - circuited fan motor
Solution
Solution steps are not shared for faults that may be dangerous.
No do-it-yourself solution is given for this fault. For your safety, call an authorised service.