Skip to content
RemFixitSearch fault code

Error code

Mitsubishi Electric PURY code 2600

No approved translation for this record yet; showing the original text.

Meaning

Water leakage from humidifier: 1) If the float switch for detecting water leakage is submerged in the water in the humidifier's drain pan and when the drain pump goes from OFF to ON, this condition is considered a preliminary water leakage. While the preliminary water leakage error is being detected, the humidifier cannot output the on signal. The discharge valve will be closed. 2) If the drain pump turns on within one hour after preliminary water leakage is detected and the above-mentioned condition is detected two consecuti

Member details

Signed-in members see the LED pattern and how to read the code with the remote control on eligible records.

View details as a member

Possible causes

(1) Water leakage through the solenoid valve for the humidifier (2) Drain water drainage problem ŒClogged drain pump ŒClogged drain piping ŒBackflow of drain water from other units (3) Stuck float switch Check for slime in the moving parts of the float switch. (4) Float switch failure (5) Humidifier relay fault ŒSolenoid valve relay drive circuit fault

Solution

Solution steps are available to members and are not shown on this page. Answer the questions to open the solution.

Remote technician support

Get help from a technician over a video call.