Error code
Mitsubishi Electric PURY code 1368
No approved translation for this record yet; showing the original text.
Meaning
Liquid side controller) (BC abnoramlity pressure: When liquid side press, sensor, gas side pressure sensor, or intermediate pressure sensor detects 30kg/cm2G (2.94MPa) or more, error stop is observed with code No. “1368”, or “1370” displayed.
Member details
Signed-in members see the LED pattern and how to read the code with the remote control on eligible records.
View details as a memberPossible causes
(1) Poor operations of indoor LEV. (2) Poor operations of BC controller LEV: Heating-only, heating-principal: LEV3, 4 Defrost: LEV3 (3) Poor operations of BC controller SVM: Cooling-only, defrost (4) Poor operations of BC controller SVA: Cooling-only, cooling-principal (5) Poor operations of BC controller SVB: Heating-only, heating-principal (6) Solenoid valve SV (3 ~ 6) trouble. Cooling-only, cooling-principal (7) Setting error of connection address. (8) Poor operations of ball valve. 10)Clogging of indoor unit filter. 11)Fall in air volume caused by dust on indoor unit fan. 12)Dust on indoor unit heat exchanger. 13)Indoor unit fan block, motor trouble. 9)~13) : Rise in high pressure caused by lowered condensing capacity in heating-only and heating-principal operation. 15)Dust on outdoor unit heat exchanger.
Solution
Solution steps are not shared for faults that may be dangerous.
No do-it-yourself solution is given for this fault. For your safety, call an authorised service.
Remote technician support
Get help from a technician over a video call.
Address of this page: https://www.remfixit.com/tr/mitsubishi-electric/pury/1368