Skip to content
RemFixitSearch fault code

Error code

Mitsubishi Electric PUHZ code EA

No approved translation for this record yet; showing the original text.

Meaning

Miswiring of Interface unit/Flow temp. controller-outdoor unit connecting wire 1. Outdoor controller circuit board can automatically check the number of connected Interface unit/Flow temp. controller. Abnormal if the number cannot be checked automatically due to miswiring of Interface unit/Flow temp. controller-outdoor unit connecting wire and etc. after power is turned on for 4 minutes. 2. Abnormal if outdoor controller circuit board recognizes excessive number of Interface unit/Flow temp. cont

Member details

Signed-in members see the LED pattern and how to read the code with the remote control on eligible records.

View details as a member

Possible causes

(1) Contact failure or miswiring of Interface unit/Flow temp. controller-outdoor unit connecting wire (2) Diameter or length of Interface unit/Flow temp. controlleroutdoor unit connecting wire is out of specified capacity. (3) Excessive number of Interface unit/Flow temp. controller is connected to 1 outdoor unit. (2 units or more) (4) Defective transmitting receiving circuit of outdoor controller circuit board (5) Defective transmitting receiving circuit of Interface/ Flow temp. controller board (6) Noise has entered into power supply or Interface/Flow temp. controller-outdoor unit connecting wire.

Solution

Solution steps are available to members and are not shown on this page. Answer the questions to open the solution.

Remote technician support

Get help from a technician over a video call.