Error code
Mitsubishi Electric PUHZ code E6
No approved translation for this record yet; showing the original text.
Meaning
Indoor/outdoor unit communication error (Signal receiving error) Abnormal if indoor controller board could 1 not receive any signal normally for 6 minutes after turning the power on. Abnormal if indoor controller board could 2 not receive any signal normally for 3 minutes. 3 Consider the unit as abnormal under the following condition. When 2 or more indoor units are connected to an outdoor unit, indoor controller board could not receive a signal for 3 minutes from outdoor controller circuit boar
Member details
Signed-in members see the LED pattern and how to read the code with the remote control on eligible records.
View details as a memberPossible causes
(1) Contact failure, short circuit or miswiring (converse wiring) of indoor/outdoor unit connecting wire (2) Defective transmitting receiving circuit of outdoor controller circuit board. (3) Defective transmitting receiving circuit of indoor controller board. (4) Noise has entered into indoor/ outdoor unit connecting wire. (5) Defective fan motor (6) Defective rush current resistor of outdoor power circuit board
Solution
Solution steps are available to members and are not shown on this page. Answer the questions to open the solution.
Remote technician support
Get help from a technician over a video call.
Address of this page: https://www.remfixit.com/tr/mitsubishi-electric/puhz/e6