Error code
Mitsubishi Electric PUHY code 7107
No approved translation for this record yet; showing the original text.
Meaning
Connection No. setting error Can not operate because connection No. of indoor unit wrongly set. Trouble source : BC controller
Member details
Signed-in members see the LED pattern and how to read the code with the remote control on eligible records.
View details as a memberPossible causes
(1) Indoor unit capacity per connector joint is exceeded as follows: Single connection : 81 or more Two connection joint : 161 or more Three connection joint : 241 or more Four connection joint : 321 or more (2) Four or more indoor units are set for the same connection. (3) The smallest connection No. has not been set when used at joint.
Solution
Solution steps are not shared for faults that may be dangerous.
No do-it-yourself solution is given for this fault. For your safety, call an authorised service.