Error code
Mitsubishi Electric PUHY code 7102
No approved translation for this record yet; showing the original text.
Meaning
Outdoor unit Error in the number of connected units The number of connected indoor units exceeds the allowable value.
Member details
Signed-in members see the LED pattern and how to read the code with the remote control on eligible records.
View details as a memberPossible causes
(1) Number of indoor units connected to the outdoor terminal block (TB3) for indoor/outdoor transmission lines exceeds limitations described below. Restriction on the Number of units number of units (1) Total number 1-13 : P220 model of indoor 1-16 : P250 models units (2) Total number of LOSSNAY units 0 or 1 (During auto address startup only) (2) The address of outdoor unit is set to 51-100 when it is the auto address (unit remote controller). "HO" will be displayed on the unit remote controller. (3) Disconnected transmission line of the outdoor unit (4) Short-circuited transmission line When (3) and (4) apply, the following display will appear. In case of network remote controller → Nothing appears on the display as no power is supplied to the remote controller. In the case of Unit remote controller → "HO" will blink.
Solution
Solution steps are available to members and are not shown on this page. Answer the questions to open the solution.
Remote technician support
Get help from a technician over a video call.