Skip to content
RemFixitSearch fault code

Error code

Mitsubishi Electric PUHY code 7100

No approved translation for this record yet; showing the original text.

Meaning

Outdoor unit Total capacity error The model total of indoor units in the system with one outdoor unit exceeds limitations.

Member details

Signed-in members see the LED pattern and how to read the code with the remote control on eligible records.

View details as a member

Possible causes

(1) The model total of indoor units in the system with one outdoor unit exceeds the following table. Model Capacity Total PUHY-P200 260 PUHY-P250 325 (2) The switch settings for the model selection of the outdoor unit are wrong. SW3-9, 3-10, 4-4

Solution

Solution steps are available to members and are not shown on this page. Answer the questions to open the solution.