Skip to content
RemFixitSearch fault code

Error code

Mitsubishi Electric PUHY code 4230

No approved translation for this record yet; showing the original text.

Meaning

Heatsink overheat protection (Detail code 125): When the heat sink temperature (THHS) remains at or above TOH is detected. models TOH INV20Y 105°C Using INV30YC 94°C | DCL temperature fault (Detail code 126)(outdoor unit): When DCL temperature that equals or exceeds 170˚C is detected (applicable to INV30YC only)

Member details

Signed-in members see the LED pattern and how to read the code with the remote control on eligible records.

View details as a member

Possible causes

(1) Fan board failure (2) Outdoor unit fan failure (3) Air passage blockage (4) THHS failure 1) (1) Fan inverter board fault (2) Outdoor unit fan fault (3) DCL temperature sensor connector contact failure (4) DCL error

Solution

Solution steps are available to members and are not shown on this page. Answer the questions to open the solution.

Remote technician support

Get help from a technician over a video call.