Meaning
Low pressure saturation temperature sensor abnormality (TH2) trouble temperature saturation pressure Low: 1. When saturation temperature sensor (TH2) detects -40˚C or less (the first time) during operations, outdoor unit stops once, mode is changed to restart mode after 3 minutes, then the outdoor unit restarts. When a temperature of -40°C 2. or less is detected again (the second time) with in 30 minutes after the first stop of outdoor unit, mode is changed to restart mode after 3 minutes, then the outdoor unit restarts. 3. When -40˚C or less temp. is detected again (the third time) within 30 minute
Member details
Signed-in members see the LED pattern and how to read the code with the remote control on eligible records.
View details as a memberPossible causes
(1) Gas leak, Gas shortage. (2) Insufficient load operations. (3) Poor operations of indoor LEV. (4) Poor operations of OC controller LEV: Cooling : LEV1 . (5) Poor operations of ball valve. (7) Clogging of indoor unit filter. (8) Fall in air volume caused by dust on indoor unit fan. (9) Dust on indoor unit heat exchanger. 10)Indoor unit block, Motor trouble. 5)~9) : Fall in low pressure caused by evaporating capacity in cooling-only cooling-principal operation. 12)Dust on outdoor heat exchanger. 13)Indoor unit fan block, motor trouble, and poor operations of fan controller. 14)~16) : Fall in low press. caused by lowered evaporating capa-city in heating-only heating-principal operation. 14)Poor operations of solenoid valve SV1. 15)Thermistor trouble (TH2~TH6). 16)Pressure sensor abnormality. 17)Control circuit board thermistor abnormality and pressure sensor input circuit abnormality. 18)Poor mounting of thermistor (TH2~TH6). - 76
Solution
Solution steps are not shared for faults that may be dangerous.
No do-it-yourself solution is given for this fault. For your safety, call an authorised service.