Skip to content
RemFixitSearch fault code

Error code

Mitsubishi Electric PUHY/PURY code 5201

No approved translation for this record yet; showing the original text.

Meaning

High-pressure sensor fault (63HS1/63HS2): ŒIf the high pressure sensor or intermediate pressure sensor detects 0.098MPa [14psi] or less during the operation, the outdoor unit stops once, turns to anti-restart mode for 3 minutes, and restarts after 3 minutes when the detected high pressure sensor or intermediate pressure sensor is 0.098MPa [14psi] or more. ŒIf the high pressure sensor or intermediate pressure sensor detects 0.098MPa [14psi] or less just before the restart, the outdoor unit makes an error stop, and the error code "5201" w | High-pressure sensor fault (Outdoor unit HPS/BC controller PS1): When a pressure sensor reading of 4.06 MPa [589 psi] or above is detected, error codes "5201" and "5203" will appear. The unit will continue its operation by using other sensors as a backup.

Member details

Signed-in members see the LED pattern and how to read the code with the remote control on eligible records.

View details as a member

Possible causes

(1) High pressure sensor failure Intermediate pressure sensor failure (2) Pressure drop due to refrigerant leak (3) Torn wire coating (4) A pin on the male connector is missing or contact failure (5) Disconnected wire (6) High pressure sensor input circuit failure on the control board (1) High pressure sensor failure

Solution

Solution steps are not shared for faults that may be dangerous.

No do-it-yourself solution is given for this fault. For your safety, call an authorised service.

Remote technician support

Get help from a technician over a video call.