Skip to content
RemFixitSearch fault code

Error code

Mitsubishi Electric PUH code EA

No approved translation for this record yet; showing the original text.

Meaning

wiring, excessive number of units (5 units or more) 1. Abnormal if the number of connected indoor units can not be set within 4 minutes after power on because of mis-wiring of indoor/outdoor unit connecting wire and the like. 2. Abnormal if outdoor controller board recognizes the number of connected indoor units as “5 units or more”.

Member details

Signed-in members see the LED pattern and how to read the code with the remote control on eligible records.

View details as a member

Possible causes

1 indoor/outdoor unit connecting wire. Diameter or length of 2 indoor/outdoor unit connecting wire is out of specified capacity. Five or more indoor units are 3 connected to one outdoor unit. Defective transmitting receiv4 ing circuit of outdoor controller board Defective transmitting receiv5 ing circuit of indoor controller board Noise has entered into power 6 supply or indoor/outdoor unit connecting wire. Remote controller is wired up 7 among indoor units (twin, triple or quadro units). Two or more outdoor units has 8 refrigerant address “0.” (In case of group control).

Solution

Solution steps are not shared for faults that may be dangerous.

No do-it-yourself solution is given for this fault. For your safety, call an authorised service.

Remote technician support

Get help from a technician over a video call.