Meaning

Abnormal low pressure (63L worked) Abnormal if connector (63L) is open (under0.03MPa) during compressor operation.

Member details

Signed-in members see the LED pattern and how to read the code with the remote control on eligible records.

View details as a member

Possible causes

(1) Gas pipe side ball valve and liquid pipe side stop valve are shut during operation. (2) Disconnection or contact failure of connector (63L) on outdoor controller board (3) Disconnection or contact failure of 63L (4) Defective outdoor controller board (5) Leakage or defective of refrigerant (6) Defective action of linear expansion valve