Meaning
Abnormal high discharging temperature Abnormal if discharging temperature thermistor (TH4) exceeds following temperature during compressor operation. Normal operation: 115:(P71-P100)/ 125:(P125,P140) or more for three minutes continuously or 135: During defrosting: 135:
Member details
Signed-in members see the LED pattern and how to read the code with the remote control on eligible records.
View details as a memberPossible causes
(1) Over-heated compressor operation caused by shortage of refrigerant (2) Defective operation of stop valve (3) Defective thermistor (4) Defective outdoor controller board (5) Defective action of linear expansion valve