Skip to content
RemFixitSearch fault code

Error code

Mitsubishi Electric PU code EC

No approved translation for this record yet; showing the original text.

Meaning

Start-up time over The unit can not finish start-up process within four minutes after power on.

Member details

Signed-in members see the LED pattern and how to read the code with the remote control on eligible records.

View details as a member

Possible causes

(1) Contact failure of indoor/outdoor unit connecting wire (2) Diameter or length of indoor/ outdoor unit connecting wire is out of specified capacity. (6) Noise has entered into power supply or indoor/outdoor unit connecting wire. (7) Remote controller is wired up among indoor units (twin, triple or quadro units). (8) Two or more outdoor units has refrigerant address “0.” (In case of group control).

Solution

Solution steps are not shared for faults that may be dangerous.

No do-it-yourself solution is given for this fault. For your safety, call an authorised service.

Remote technician support

Get help from a technician over a video call.