Error code
Mitsubishi Electric PU code E4
No approved translation for this record yet; showing the original text.
Meaning
Remote controller signal receiving error Abnomal if indoor controller board can 1 not receive normally any data from remote controller or from other indoor controller board for three minutes. Indoor controller board can not receive 2 any signal from remote controller for two minutes.
Member details
Signed-in members see the LED pattern and how to read the code with the remote control on eligible records.
View details as a memberPossible causes
(1) Contact failure at transmission wire of remote controller (2) All remote controllers are set as “sub” remote controller. In this case, E0 is displayed on remote controller, and E4 is displayed at outdoor LED. (3) Defective transmitting receiving circuit of remote controller (4) Defective transmitting receiving circuit of indoor controller board (5) Noise has entered into the transmission wire of remote controller. (6) Remote controller is connected to the unit once, and removed without power reset. (7) Wiring regulations are not observed. Refer to (2) The transmitting specification for “A” control on page 59. •Length of wires •Number of remote controllers •Diameter of wires •Number of indoor units
Solution
Solution steps are available to members and are not shown on this page. Answer the questions to open the solution.
Remote technician support
Get help from a technician over a video call.
Address of this page: https://www.remfixit.com/tr/mitsubishi-electric/pu/e4