Mitsubishi Electric PU code 5300

No approved translation for this record yet; showing the original text.

Meaning

Current sensor error Abnormal if compressor current is not detected on first compressor start-up after power supply is put on.

Member details

Signed-in members see the LED pattern and how to read the code with the remote control on eligible records.

View details as a member

Possible causes

(1) Disconnection or contact failure of connector (52C) on outdoor controller board (2) Disconnection or contact failure of coil 52C (3) Defective outdoor controller board (4) Defective parts of 52C (5) Compressor V-phased wire does not penetrate through current detector.

Solution

Solution steps are not shared for faults that may be dangerous.

No do-it-yourself solution is given for this fault. For your safety, call an authorised service.

Remote technician support

Get help from a technician over a video call.