Skip to content
RemFixitSearch fault code

Error code

Mitsubishi Electric PU code 1102

No approved translation for this record yet; showing the original text.

Meaning

Abnormal high discharging temperature Abnormal if discharging temperature thermistor (TH4) exceeds following temperature during compressor operation. Normal operation: 115:(P25-P100)/ 125:(P125,P140) or more for three minutes continuously or 135: During defrosting: 135:

Member details

Signed-in members see the LED pattern and how to read the code with the remote control on eligible records.

View details as a member

Possible causes

(1) Over-heated compressor operation caused by shortage of refrigerant (2) Defective operation of stop valve (3) Defective thermistor (4) Defective outdoor controller board (5) Defective action of linear expansion valve

Solution

Solution steps are not shared for faults that may be dangerous.

No do-it-yourself solution is given for this fault. For your safety, call an authorised service.

Remote technician support

Get help from a technician over a video call.