Skip to content
RemFixitSearch fault code

Error code

Mitsubishi Electric PQRY code 7102

No approved translation for this record yet; showing the original text.

Meaning

Heat source Error in the number of connected units unit The number of connected to the heat source units exceeds the allowable value.

Member details

Signed-in members see the LED pattern and how to read the code with the remote control on eligible records.

View details as a member

Possible causes

(1) Number of indoor units connected to the heat source unit terminal block (TB3) for indoor/outdoor transmission lines exceeds limitations described below. Restriction on the Number of units number of units (1) Total number of 1-15 : 200 model indoor units 1-16 : 250 model (2) Total number of indoor units + 1-35 Fresh Master + M-NET remote controllers (3) Total number of 1 BC controllers (4) Total number of Fresh Master + LOSSNAY 0 or 1 (During auto address start-up only) (2) The address of heat source unit is set to 51-100 when it is the auto address (MA remote controller (MA)). "HO" will be displayed on the MA remote controller (MA). (3) Disconnected transmission line of the heat source unit (4) Short-circuited transmission line When (3) and (4) apply, the following display will appear. ŒIn case of M-NET remote controller → Nothing appears on the display as no power is supplied to the M-NET remote controller. ŒIn the case of MA remote controller (MA) → "HO" will blink. (5) Disconnected transmission line of the BC controller.

Solution

Solution steps are available to members and are not shown on this page. Answer the questions to open the solution.

Remote technician support

Get help from a technician over a video call.