Meaning

Intermediate pressure sensor fault (BC controller PS3): When a pressure sensor reading of 4.06 MPa [589 psi] or above OR 0.98Mpa[142psi] or below is detected, error codes "5201" OR "5203" will appear. The unit will continue its operation by using other sensors as a backup.

Member details

Signed-in members see the LED pattern and how to read the code with the remote control on eligible records.

View details as a member

Possible causes

(1) High pressure sensor failure (2) Torn wire coating (3) A pin on the male connector is missing or contact failure (4) Disconnected wire (5) High pressure sensor input circuit failure on the control board

Solution

Solution steps are not shared for faults that may be dangerous.