Mitsubishi Electric PQRY code 5201
No approved translation for this record yet; showing the original text.
Meaning
High-pressure sensor fault (63HS1): If the high pressure sensor detects 0.098MPa [14psi] or less during the operation, the heat source unit stops once, turns to anti-restart mode for 3 minutes, and restarts after 3 minutes when the detected high pressure sensor is 0.098MPa [14psi] or more. If the high pressure sensor detects 0.098MPa [14psi] or less just before the restart, the heat source unit makes an error stop, and the error code "5201" will appear. During 3-minute antirestart mode, preliminary errors will be displayed on t | High-pressure sensor fault (BC controller PS1): When a pressure sensor reading of 4.06 MPa [589 psi] or above OR 0.98Mpa[142psi] or below is detected, error codes "5201" OR "5203" will appear. The unit will continue its operation by using other sensors as a backup.
Member details
Signed-in members see the LED pattern and how to read the code with the remote control on eligible records.
View details as a memberPossible causes
(1) High pressure sensor failure (2) Pressure drop due to refrigerant leak (3) Torn wire coating (4) A pin on the male connector is missing or contact failure (5) Disconnected wire (6) High pressure sensor input circuit failure on the control board (2) Torn wire coating (3) A pin on the male connector is missing or contact failure (4) Disconnected wire (5) High pressure sensor input circuit failure on the control board
Solution
Solution steps are not shared for faults that may be dangerous.
No do-it-yourself solution is given for this fault. For your safety, call an authorised service.
Remote technician support
Get help from a technician over a video call.
Address of this page: https://www.remfixit.com/tr/mitsubishi-electric/pqry/5201