Error code
Mitsubishi Electric PQHY code 4260
For your safety
This fault is rated critical. No remote repair or do-it-yourself instructions are given; do not use the appliance or try to open or repair it.
Hazard area: mains voltage
If there is a risk to life, first move to a safe place, then call 112. Do not follow remote repair instructions.
Call 112The emergency numbers here are for Turkey. If you are outside Turkey, call your local emergency number.
No approved translation for this record yet; showing the original text.
Meaning
Cooling fan abnormality: When the DC bus current (DCCT) 200A or more is detected When the DC bus current abnormality VDC 350V or more or VDC 190V or less is detected When the heat sink temperature (THHS1) 60°C [140°F] or more is detected for 10 or more minutes at inverter startup
Member details
Signed-in members see the LED pattern and how to read the code with the remote control on eligible records.
View details as a memberPossible causes
(1) Inverter output related (1) Same as 4220 error (2) G/A board failure (3) Electrolytic capacitor (C1) failure (1) Same as 4230 error (2) THHS failure (3) INV board failure
Solution
Solution steps are not shared for faults that may be dangerous.
No do-it-yourself solution is given for this fault. For your safety, call an authorised service.
Address of this page: https://www.remfixit.com/tr/mitsubishi-electric/pqhy/4260