Error code
Mitsubishi Electric PQHY/PQRY code 6846
No approved translation for this record yet; showing the original text.
Meaning
Start-up time over: Start-up time over The unit cannot finish start-up process within 4 minutes after power on.
Member details
Signed-in members see the LED pattern and how to read the code with the remote control on eligible records.
View details as a memberPossible causes
(1) Contact failure of indoor/heat source unit connecting wire (2) Diameter or length of indoor/heat source unit connecting wire is out of specified capacity. (3) 2 or more heat source units have refrigerant address "0". (In case of group control) (4) Noise has entered into power supply or indoor/heat source unit connecting wire.
Solution
Solution steps are not shared for faults that may be dangerous.
No do-it-yourself solution is given for this fault. For your safety, call an authorised service.
Remote technician support
Get help from a technician over a video call.
Address of this page: https://www.remfixit.com/tr/mitsubishi-electric/pqhy-pqry/6846