Meaning

Drain sensor (Thd) fault: ŒIf the open or short circuit of the thermistor has been detected for 30 seconds, this condition is considered to be a preliminary error, and the unit goes into the 3-minute restart delay mode. ŒIf another episode of the above condition is detected during the preliminary error, this is considered a drain sensor error.(If the short or open circuit of the thermistor is no longer detected, normal operation will be restored in 3 minutes.) ŒThis error is detected when one of the following conditions

Member details

Signed-in members see the LED pattern and how to read the code with the remote control on eligible records.

View details as a member

Possible causes

(1) Faulty connector (CN31) insertion. (2) Broken or semi-broken thermistor wire (3) Thermistor failure (4) Indoor unit control board (error detection circuit) failure